First, the scope
DZ47GQ-63 series over-voltage protection circuit breaker is DZ47-63 Small circuit breakers installed voltage module derived products. For rated current 1-63A, AC 50Hz, rated voltage of 230V circuit, over-voltage protection setting value (275 ± 5%), undervoltage protection rating of 170 ± 5%, lines for buildings and facilities AC power distribution systems and electrical equipment over-current overload, short circuit and over, under voltage protection purposes. Residential, hotels hospitals, shops, the best products installed within the office.Two other derivative products: DZ47G-63 Overvoltage ; DZ47Q-63 Overvoltage .
two, brownouts automatic controller Models and Specifications
Third, the structural characteristics
◆ DZ47 over-voltage protection circuit breaker by the shell, operating mechanism, heat release, electromagnetic release contact system, arc system, with over-voltage protection circuit boards and other components, overload and short circuit protection, unique design.◆ DZ47 over-voltage protection products with rated short-circuit 4500A breaking capacity, mechanical life of 20,000 times or more, and product appearance. Standard mounting rails as TH35-7.5 just mounting rail.
◆ DZ47 over voltage circuit breaker has the following characteristics: a safe and comfortable handle operation, over-under voltage protection value can be set according to user requirements fixed, must pay attention to the wiring zero FireWire; progress under the power, in line with the characteristics of the power line, easy to install.
Fourth, the main technical parameters
Name | frame degree rated current | Poles | Rated voltage (V) | Rated Current (A) | breaking current Icu (A) | protection action value (V) | Instantaneous Trip type |
DZ47 -63G | 63A | 1P + N | 230 | 1-63 | 6000 | 270 ± 5% | B, C |
DZ47 -63Q | 170 ± 5% | ||||||
DZ47 -63GQ | 270 ± 5% 170 ± 5% |
< td style = "font-family: Microsoft elegant black, Times New Roman, Arial; font-size: 12px; color: rgb (51, 51, 51); margin: 0px; padding: 0px;" align = "center" bgcolor = " #cccccc "width =" 25% "> standard
Name | code | use | |
< strong> Brown-breaker | DZ47Q-63 | When the supply voltage drops between 170V ± 5%, so that the circuit-breaker, to achieve the line under-voltage protection. | IEC60947-2: 1999, GB14048.2-2001 |
< strong> overpressure breaker | DZ47G-63 | When the power supply voltage up to 270V ± 5% when the circuit breaker tripping, achieve line overvoltage protection | IEC60947-2: 1999 , GB14048.2-2001 |
< strong> over-voltage circuit breaker is | DZ47GQ-63 | When 220V rated supply voltage up to 270 ± 5% or dropped during 170V ±± 5%, so that the circuit breaker tripping, achieve line protection. | IEC60947-2: 1999, GB14048.2-2001 |
Six, shape and installation dimensions
Eight, ordering instructions
when ordering indicate the following points:
Product type and name: If DZ47GQ-63 over-voltage protection circuit breaker
Rated current/power: as 63A.
Order number: as 380.
Ordering example: DZ47GQ-63 over-voltage protection circuit breaker , 20A, 2560 只.