First, the scope
YDZ20Y Series Molded Case Circuit Breaker to do with shunt trip ( YDZ20Y MCCB ), applicable to the exchange 50Hz, rated insulation voltage 660V, rated working voltage 380V (400V) and the following circuit, the rated current from 16A to 1250A. Generally used as a distribution, in which Y, J, Q-type and rated current of 225A and below the frame for the shell type circuit breaker 400Y may be used as motor protection. Under normal circumstances, the circuit breaker can be used as infrequent line conversion and motor are not infrequent start.Quadrupole YDZ20 MCCB is mainly used for AC 50Hz, rated voltage 400V and below, rated current of 16A to 630A three-phase four-wire system, which can ensure that users and the power is completely disconnected, To ensure safety, so as to solve any other insurmountable breaker neutral pole current is not zero defects.
YDZ20 molded case circuit breakers in the distribution network used to distribute power, and can be used as power lines and equipment overload, short circuit and under voltage protection.
Motor protection circuit breakers used in the distribution network squirrel cage motor starting and breaking as well as motor overload, short circuit and under voltage protection.
The series frame degree rated current of the transparent cover from the three-pole 100A-630A product but also with, customers can freely observe the internal operation of the product.
YDZ20 MCCB in line GB14048.2 standards. & Nbsp;
Second, model and specification
Type Meaning Note:
. a distribution no code breaker: motor protection circuit breaker with 2 represents;
. b handle direct operation No code: electric operation indicated by P; Z represents by turning the handle (Frame rating of 1250A product without turning the handle);
. c Press the rated ultimate short-circuit breaking capacity high and low points: C Cheap; Y general type; J higher type; G highest type;
Third, the accessory code
Attachment Name | instantaneous release | double release |
without attachments | 200 | 300 |
alarm contacts | 208 | 308 |
shunt release | 210 | 310 |
auxiliary contacts | 220 | 320 |
undervoltage release | 230 | 330 |
Shunt release Auxiliary contact | 240 | 340 |
Shunt release Undervoltage release | 250 | 350 |
two auxiliary contacts | 260 | 360 |
auxiliary contact undervoltage release | 270 | 370 |
Shunt release Alarm contact | 218 | 318 |
Auxiliary contact Alarm contact | 228 | 328 |
undervoltage release alarm contacts | 238 | 338 |
Shunt release Auxiliary contact Alarm contact | 248 | 348 |
shunt release undervoltage release alarm contacts | 258 | 358 |
two auxiliary contact alarm contacts | 268 | 368 |
undervoltage release Auxiliary contact Alarm contact | 278 | 378 |
Fourth, the structural features
◆ YDZ20 molded case circuit breakers for the basic product is a Y-type, consisting of four part insulation shell, operating mechanism, contact system and tripping composition. The operating mechanism of the circuit breaker has the contacts and breaking the fast closing function, the "together", "minute", "re-label" and "free trip" position to the handle position to distinguish.◆ C type, J and G YDZ20 breaker is in the Y-derived products based on the basic design is made (except C-160A outside). J-breaker is the Y-breaker contacts for structural improvements, so that in the case of short, before the agency action, moving quickly off the contact, to achieve the purpose of improving on-off capabilities.
Repulsion limiting the contact system ◆ G-breaker with a parallel conductor plate in Y-breaker after a series of composition, the system longer than the J-type contact repulsion, disconnect the distance is large, and therefore can more quickly limiting; in normal disconnect closed and in setting short-circuit trip protection action value range, by Y-type circuit breaker to complete. Once the large current or large short-circuit current in the network, the series of repulsion limiting contact quickly denounced by the electric power and open, while limiting the introduction of the arc. Denounced the contacts open process, release action, the operating mechanism of the circuit breaker so that Y-type contact breaking. Repulsion limiting the contact is due to the reduction or disappearance of current and return to the closed state.
◆ quadrupole YDZ20 MCCB neutral pole (N) is not installed tripping element, located in the right position. In the division process, the neutral pole is defined as representing a closed first contact with the other three poles, representing the other three poles disconnected after opening.
◆ C-type circuit breaker is designed to meet and below 630kVA transformer power distribution grid needs protection, through the selection of materials and simplify the structure of the economy and improvement of technology and other measures, to achieve better economic results.
Fifth, the main parameters and technical performance
1, basic parameters CM1L MCCBType | Poles | short circuit breaking capacity level | short circuit breaking capacity KA (V) | rated current ln (A) | |
lcu/cosφ | lcu/cosφ | ||||
YDZ20C-160 | 3P | C | 12/0.30 | - | 16,20,25,32,40,50,63,80,100,125,160 |
YDZ20Y-100 | 3P | Y | 18/0.30 | 14/0.30 | 16,20,25,32,40,50,63,80,100 |
YDZ20J-100 | 3P, 4P | J | 35/0.25 | 18/0.30 | |
YDZ20G-100 | 3P | G | 100/0.20 | 50/0.25 | |
YDZ20C-225 | 3P | C | 15/0.30 | - | 100,125,160,180,200,225,250 |
YDZ20Y-225 | 3P | Y | 25/0.25 | 19/0.30 | 100,125,160,180,200,225 |
YDZ20J-225 | 3P, 4P | J | 42/0.25 | 25/0.25 | |
YDZ20G-225 | 3P | G | 100/0.20 | 50/0.25 | |
YDZ20C-400 | 3P | C | 20/0.30 | - | 100,125,160,180,200,250,315,350,400 |
YDZ20Y-400 | 3P | Y | 30/0.25 | 23/0.25 | 200,250,315,350,400 |
YDZ20J-400 | 3P, 4P | J | 42/0.25 | 25/0.25 | |
YDZ20G-400 | 3P | G | 100/0.20 | 50/0.25 | |
YDZ20Y-630 | 3P | Y | 30/0.25 | 23/0.25 | 400,500,630 |
YDZ20J-630 | 3P, 4P | J | 50/0.25 | 25/0.25 | |
YDZ20Y-1250 | 3P | Y | 50/0.25 | 32.5/0.25 | 630,700,800,1000,1250 |
YDZ20J-1250 | 3P | J | 60/0.2 | 32.5/0.25 | 800,1000,1250 |
★ short-circuit protection circuit breaker current setting
Type | power distribution | motor protection |
YDZ20 Y/J/G-100 | 10ln | 12ln |
YDZ20 Y/J/G-225 | 5ln and 10ln | 12ln |
YDZ20-400 | 10ln | 12ln |
YDZ20 J/G-400 | 5ln and 10ln | - |
YDZ20 Y/J-630 | 5ln and 10ln | - |
YDZ20 Y/J-1250 | 4ln and 7ln | - |
2, YDZ20Y.JG-100 circuit breakers, when In≤40A, instantaneous action current level action is 600A, non-operating current is 10In.
★ inverse power distribution circuit breaker disconnect feature
ID | test current Title | Tuning Current multiple |
agreed time | initial state | |
In≤63 | In & gt; 63 | ||||
1 | conventional non-tripping current | 1.05In | ≥1h | ≥2h | cold |
2 | Conventional tripping current | 1.30In | <1h | <2h | No. 1 test immediately after the start |
★ motor protection circuit breaker disconnect inverse characteristic
ID | test current Title | Setting current multiples | agreed time | initial state |
1 | conventional non-tripping current | 1.0In | ≥2h | cold |
2 | Conventional tripping current | 1.2In | & lt; 2h | No. 1 test immediately after the start |
◆ Shunt release:
◇ rated control supply voltage: AC220V, 380V, DC24V, 110V, 220V.
◇ when between 70 and 110% of rated control supply voltage, shunt trip circuit breaker tripping should be reliable.
◇ NOTE: When the selection voltage specifications DC24V, rated current should reach 5A ± 10%
◆ undervoltage release:
◇ rated working voltage: AC220V, 380V. When the voltage drops (or even slow decline) to 70% to 35% of rated voltage, under-voltage release shall operate at below 35% of rated voltage release, undervoltage release should be able to prevent disconnection is closed, the power supply voltage is equal to or greater than 85%, should be able to ensure that the circuit breaker off.
◆ alarm contacts:
◇ rated working voltage: AC220V, thermal current: 1A.
◆ auxiliary contacts: at different fashion undervoltage releases and shunt releases can be mounted auxiliary contacts. Auxiliary contacts rating (see table);
◇ making and breaking capacity (see table): The same auxiliary contact is not energized operating performance and the number of circuit breakers, power times the number of operations for the 6050, when the circuit breaker operating performance number is less than 6050 times, then the circuit breaker equal.
frame degree rated current | Conventional thermal current (A) | rated current (A) | |
AC380V | DC220V | ||
400A and above | 6 | 3 | 0.2 |
250A and below | 3 | 0.26 | 0.14 |
Use Type |
ON I/Ie |
ON U/Ue |
ON cosφ |
ON | Breaking | Breaking | Breaking | Breaking | operating frequency (Times/h) |
energized Time (s) |
T0.95ms | I/Ie | U/Ue | cosφ | T0.95 | ||||||
AC-15 | 10 | 1 | 0.3 | |
1 | 1 | 0.3 | |
120 | 0.05-2 |
AC-13 | 1 | 1 | |
6 × Pe | 1 | 1 | |
6 × Pe | 120 | 0.05-2 |
External accessories
★ breaker ★ electric operation after the relevant parameters and installation of electric breaker operating mechanism total height H Table.
Type | YDZ20Y, J-100 | YDZ20G-100 | YDZ20Y, J-225 | YDZ20G-225 | YDZ20Y-400 | YDZ20J-400 YDZ20Y, J-630 |
YDZ20G-400 | YDZ20Y, J-1250 |
height H | 185 | 235 | 220 | 305 | 230 | 245 | 345 | 275 |
structure | Solenoid | Motor | |
|||||
voltage specifications | AC50Hz, 220V, 380V | |||||||
Note: The circuit breaker with motorized operating mechanism trip trip, the electric circuit breaker operating mechanism must be deducted before closing! |
★ size table manually operated mechanism mounted.
Type | YDZ20Y, J, G-100 | YDZ20Y, J, G-225 | YDZ20Y-400 | YDZ20J, G-400 YDZ20Y, J-630 |
Installation dimensions H | 55 | 85 | 105 | 80 |
center operating handle with respect to the circuit breaker X value | 0 | 0 | 0 | 0 |
six, YDZ20 breaker structural features
YDZ20 MCCB is a Y-shaped basic products, from insulation shell, operating mechanism, contact system and the release of four components. The operating mechanism of the circuit breaker has the contacts and breaking the fast closing function, the "together", "minute", "re-label" and "free trip" position to the handle position to distinguish.C-type, J-type and G-type circuit breaker is in the Y-derived products based on the basic design is made (except C-160A outside). J-breaker is the Y-breaker contacts for structural improvements, so that in the case of short, before the agency action, moving quickly off the contact, to achieve the purpose of improving on-off capabilities.
G-type circuit breaker is repulsion limiting the contact system of a parallel conductor plate Y-breaker after a series of composition, the system longer than the J-type contact repulsion, distance big disconnect, thus limiting more quickly stream; Under normal disconnect closed and the trip short circuit protection action setting value range, by Y-type circuit breaker to complete. Once the large current or large short-circuit current in the network, the series of repulsion limiting contact quickly denounced by the electric power and open, while limiting the introduction of the arc. Denounced the contacts open process, release action, the operating mechanism of the circuit breaker so that Y-type contact breaking. Repulsion limiting the contact is due to the reduction or disappearance of current and return to the closed state.
Four-pole circuit breaker neutral pole (N) is not installed tripping element, located in the right position. In the division process, the neutral pole is defined as representing a closed first contact with the other three poles, representing the other three poles disconnected after opening.
C Type YDZ20 breaker is designed to meet and below 630kVA transformer grid distribution protection needs, through the selection of materials and simplify the structure of the economy and improvement of technology and other measures, to achieve better economic results.
seven, YDZ20 Breaker shape and installation dimensions
Type | Dimensions (mm) | ||||||||||||||
Front connection | |||||||||||||||
W | L | H | W1 | L1 | L2 | H1 | H2 | H3 | W2 | L4 | L5 | H6 | |||
3P | 4P | 3P | 4P | ||||||||||||
YDZ20Y-100 | 105 | - | 165 | 86.5 | 70 | - | - | 215 | 103 | 26.5 | 26.5 | 26 | 69 | 28.5 | 4 |
YDZ20J-100 (W) | 105 | 140 | 165 | 86.5 | 70 | 105 | - | 215 | 103 | 26.5 | 26.5 | 26 | 69 | 28.5 | 4 |
YDZ20G-100 | 105 | - | 165 | 140 | 70 | - | - | 218.5 | 156.5 | 26.5 | 80.5 | 26 | 69 | 28.5 | 4 |
YDZ20C-160 | 108 | - | 155 | 84 | 70 | - | - | - | 106.5 | 34 | 34 | 30 | 66 | 32 | 4.5 |
YDZ20Y-225 | 109 | - | 256.5 | 105 | 70 | - | 329 | 402 | 142 | 19.5 | 19.5 | 35 | 89 | 53 | 6.5 |
YDZ20J-225 (W) | 109 | 144 | 256.5 | 105 | 70 | 105 | 329 | 402 | 142 | 19.5 | 19.5 | 35 | 89 | 53 | 6.5 |
YDZ20G-225 | 109 | - | 256.5 | 187 | 70 | - | 329 | 402 | 227 | 38 | 103.5 | 35 | 89 | 53 | 6.5 |
YDZ20C-250 | 109 | - | 208 | 105 | 70 | - | 300 | - | 142 | 19.5 | 19.5 | 35 | 89 | 44 | 6 |
YDZ20C-400 | 155 | - | 276 | 112 | 102 | - | 391 | 450 | 149.5 | 32.5 | 32.5 | 52 | 88 | 72 | 5 |
YDZ20Y-400 (W) | 155 | - | 276 | 112 | 102 | - | 391 | 450 | 149.5 | 32.5 | 32.5 | 52 | 88 | 72 | 5 |
YDZ20J-400 (W) | 210 | 280 | 268 | 112 | 140 | 210 | 378 | 425 | 150 | 21.5 | 21.5 | 62 | 90 | 55 | 5.5 |
YDZ20G-400 | 210 | - | 268 | 208 | 140 | - | 378 | 394 | 247 | 75 | 121.5 | 62 | 90 | 55 | 5.5 |
YDZ20C-630 | 210 | - | 268 | 112 | 140 | - | 378 | 425 | 150 | 21.5 | 21.5 | 62 | 90 | 55 | 5.5 |
YDZ20Y-630 (W) | 210 | - | 268 | 112 | 140 | - | 378 | 425 | 150 | 21.5 | 21.5 | 62 | 90 | 55 | 5.5 |
YDZ20J-630 (W) | 210 | 280 | 268 | 112 | 140 | 210 | 378 | 425 | 150 | 21.5 | 21.5 | 62 | 90 | 55 | 5.5 |
YDZ20Y-1250 | 210 | - | 406 | 122 | 140 | - | 548 | 588 | 180 | 26 | 26 | 78 | 100 | 143 | 16 |
YDZ20J-1250 | 210 | - | 406 | 122 | 140 | - | 548 | 588 | 180 | 26 | 26 | 78 | 100 | 143 | 16 |
Type | Dimensions (mm) | Installation dimensions (mm) | ||||||
Front connection | ||||||||
W1 | L3 | H4 | H5 | A | B | φd | ||
3P | 4P | |||||||
YDZ20Y-100 | 70 | - | 147 | 55.5 | 55.5 | 35 | 126 | 5 |
YDZ20J-100 (W) | 70 | 105 | 147 | 55.5 | 55.5 | 35 | 126 | 5 |
YDZ20G-100 | 70 | - | 147 | 55.5 | 55.5 | 35 | 126 | 5 |
YDZ20C-160 | 70 | - | 141 | 64 | 64 | 35 | 135 | 4.5 |
YDZ20Y-225 | 70 | - | 212.5 | 47 | 90 | 35 | 196.5 | 4.5 |
YDZ20J-225 (W) | 70 | 105 | 212.5 | 47 | 90 | 35 | 196.5 | 4.5 |
YDZ20G-225 | 70 | - | 212.5 | 47 | 100 | 35 | 196.5 | 4.5 |
YDZ20C-250 | 70 | - | 184 | 75 | 128 | 35 | 172 | 4.5 |
YDZ20C-400 | 102 | - | 247 | 80 | 125 | 51 | 240 | 7 |
YDZ20Y-400 (W) | 102 | - | 247 | 80 | 125 | 51 | 240 | 7 |
YDZ20J-400 (W) | 140 | 210 | 233 | 90 | 90 | 70 | 200 | 7 |
YDZ20G-400 | 140 | - | 233 | 85 | 119 | 70 | 200 | 7 |
YDZ20C-630 | 140 | - | 233 | 92 | 92 | 70 | 200 | 7 |
YDZ20Y-630 (W) | 140 | - | 233 | 92 | 92 | 70 | 200 | 7 |
YDZ20J-630 (W) | 140 | 210 | 233 | 92 | 92 | 70 | 200 | 7 |
YDZ20Y-1250 | 140 | - | 375 | - | - | 70 | 375 | 9 |
YDZ20J-1250 | 140 | - | 375 | - | - | 70 | 375 | 9 |
Nine, ordering instructions
When ordering indicate the following points:
Product type and name: If YDZ20 MCCB -630/3318
Instantaneous tripping Current Rating: such as 630A.
Breaker attachment names, specifications, combination code, adopted when the undervoltage release and shunt trip, should indicate the operating voltage (or control supply voltage) value;
Uses: power distribution
Wiring: rear Front connection, Rear connection.
Poles: 4P
Order number: as 230.
Ordering example: YDZ20 -630/3318,4P, AC380V, 630A, 3500 只.